Size : 16mm to 90mm & ½” to 3 ½”
Standard : EN60079-0:2012+A11:2013, En60079- 1:2014, EN60079-31:2014
Application : For indoor & outdoor hazardous area use with all types of Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Wire Braid Armour, Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Armoured & Jacketed providing flameproof seal on cable inner sheath and environmental seal on cable outer sheaths. Also provides mechanical retention & electrical continunty via armour wire termination with rotating rigid conduit connection facility.
Code of Protection : Ex db IIC Gb, Ex tb IIIC Db
Ingress Protection : IP66 as per EN 60529.
Operating Temp. : -60°C to +135°C
Material : Brass CW614N/CW617N/EN12165, Stainless Steel 316L
Thread : Metric, NPT, BSP, ET and PG
Cable Type :Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Wire Braid Armour, Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid.
Features : Displacement Seal and Armoured Ring
Seal Material : LSOH Silicone Seal & LSOH Nylon Washer
Accessories : PVC Shroud, Earth Tag, Thread Seal, Serrated Washer.
E1FURM Ex “d” Cable Gland
For indoor & outdoor hazardous area use with all types of Single Wire Armour (SWA), Aluminium Wire Armour (AWA), Pliable Wire Armour (PWA), Steel Tape Armour (STA), Wire Braid Armour, Aluminium Strip Armour (ASA), Screened Flexible (EMC) Wire Braid (e.g. CY / SY), Armoured & Jacketed providing flameproof seal on cable inner sheath and environmental seal on cable outer sheaths. Also provides mechanical retention & electrical continunty via armour wire termination with rotating rigid conduit connection facility.
Reviews
There are no reviews yet.